WPET-500 series of electronic load adjusters is working as governor For small hydraulic generator sets that operate independently power Network in large remote mountainous areas, villages etc. This Device can transfer load, balance input power and output power, and Keep a constant run speed (constant frequency) of generator sets Without guide blade or governor. Compared to the conventional Mechanical and hydraulic speed control device, the essential Difference is that the fully electronic control without mechanical Adjustment and the power balance without changing water turbine flow Can effectively keep a certain rotating speed. Electronic load Adjuster can both simplify the structure of hydraulic turbine and Reduce the cost. It is also of higher automatic level. Besides, load Adjustment panel that consists of the automatic load adjustment Function of electronic load adjuster can suppress the load Fluctuation of the power network and can greatly improve the Operation stability when small generator sets are running on Isolated network.
PARTICULAR INFO I, MAIN PERFORMANCE AND CHARACTERISTICS The overall design and System configuration are implemented guided by the goal of " rimary Computer control, accompanied by manual control"; Over-current, Over-voltage, under - voltage, converse power, low frequency, over Frequency, PT and CT wire-break protection of generator compound Voltage; Turbine bearing temperature, shear pin, cooling water Protection and etc; The system configuration and equipment Selection take the leaping development of computer into Consideration. It is advanced and upward compatible. Modular and Structural software guarantee system extension to satisfy the Requirements of adding new functions and expand the scale; Sequence control and closed-loop regulation, one button starting; Compact structure, simple installation, labor-saving and Material-saving, less occupation of space and simple operation; Goode performance of real time and anti - interference, suitable For field conditions; Can running without Master computer. II, ORDER INFORMATION, Single line diagram should be provided in Advance; , Schematic diagram and terminal diagram of equipment Operation should be provided; , Other specific requirements.